The No. 3 heater control sub-assembly is powered through the ECU-IG1 No. 4 fuse. The No. 3 heater control sub-assembly transmits operational signals of each switch to the air conditioning amplifier assembly.
| Symptom | Factor |
|---|---|
·
A/C switch indicator is abnormal ·
Hot air does not come out even though temperature control switch set to MAX HOT ·
Idle up not performed even though temperature control switch set to MAX COOL |
·
No. 3 heater control sub-assembly malfunction ·
Air conditioning amplifier assembly malfunction ·
Harness or connector |
Inspect the fuses for circuits related to this system before performing the following procedure.
Remove the No. 3 heater control sub-assembly.
Inspect the No. 3 heater control sub-assembly.
| Proceed to |
|---|
| OK |
| NG |
OK
NG
Measure the voltage according to the value(s) in the table below.
| Tester Connection | Condition | Specified Condition |
|---|---|---|
| I159-1 (IG+) - Body ground | Ignition switch on (IG) | 11 to 14 V |
| I159-1 (IG+) - Body ground | Ignition switch off | Below 1 V |
| Proceed to |
|---|
| OK |
| NG |
OK
NG
Choose the problem to be inspected.
| Result | Proceed to |
|---|---|
| A/C switch indicator is abnormal | A |
| Hot air does not come out even though temperature control switch set to MAX HOT | B |
| Idle up not performed even though temperature control switch set to MAX COOL | C |
A
B
C
Disconnect the I162 air conditioning amplifier assembly connector.
Measure the resistance according to the value(s) in the table below.
| Tester Connection | Condition | Specified Condition |
|---|---|---|
| I159-8 (A/C) - I162-32 (A/C) | Always | Below 1 Ω |
| I159-4 (AIND) - I162-4 (LED) | Always | Below 1 Ω |
| I159-8 (A/C) or I162-32 (A/C) - Other terminals and body ground | Always | 10 kΩ or higher |
| I159-4 (AIND) or I162-4 (LED) - Other terminals and body ground | Always | 10 kΩ or higher |
| Proceed to |
|---|
| OK |
| NG |
OK
NG
Disconnect the I162 air conditioning amplifier assembly connector.
Measure the resistance according to the value(s) in the table below.
| Tester Connection | Condition | Specified Condition |
|---|---|---|
| I159-2 (MAXH) - I162-30 (HEAT) | Always | Below 1 Ω |
| I159-2 (MAXH) or I162-30 (HEAT) - Other terminals and body ground | Always | 10 kΩ or higher |
| Proceed to |
|---|
| OK |
| NG |
OK
NG
Disconnect the I162 air conditioning amplifier assembly connector.
Measure the resistance according to the value(s) in the table below.
| Tester Connection | Condition | Specified Condition |
|---|---|---|
| I159-7 (MAXC) - I162-31 (COOL) | Always | Below 1 Ω |
| I159-7 (MAXC) or I162-31 (COOL) - Other terminals and body ground | Always | 10 kΩ or higher |
| Proceed to |
|---|
| OK |
| NG |
OK
NG